Wire Gauge Calculator | AWG Size & Voltage Drop

Quick Start Guide

  1. Enter circuit current: The current the wire must safely carry in Amperes.
  2. Specify run distance: One-way distance from source to load in feet or meters.
  3. Set voltage: System voltage (120V, 240V, 480V, etc.).
  4. Get recommended gauge: See wire size, voltage drop, and safety verification.

Understanding Wire Gauge & Voltage Drop

The AWG scale runs backwards

American Wire Gauge is counterintuitive: a smaller number means a thicker wire. 10 AWG carries far more current than 20 AWG. Thicker wire has lower resistance, so it wastes less energy as heat and drops less voltage over a given run length.

Looking up a gauge you already have

Sizing runs one way — amps in, gauge out. The ampacity lookup runs the other: choose a gauge and see the maximum current it may carry under the conditions you have already set. Both directions use the same NEC Table 310.16 figures and the same 310.15(B)(1) ambient correction, so they cannot disagree about a conductor. The number shown is the derated one, and the panel says whether the table or the ambient temperature is what limits it. Copper and aluminum each use their own NEC Table 310.16 column, so an aluminum run is rated against aluminum figures — roughly 78% of copper for the same size. Two combinations the code does not rate are reported as such rather than as a number: aluminum below 12 AWG (copper is rated from 14 AWG, aluminum only from 12), and aluminum in free air.

Two separate limits: ampacity and voltage drop

Ampacity is a safety limit — the maximum current a wire can carry before its insulation overheats. Voltage drop is a performance limit — how much the wire's own resistance "eats" the voltage over distance, which can starve a device even on a wire that is otherwise safe. A wire can pass one check and fail the other, so this calculator checks both and recommends whichever gauge is larger.

Recommended voltage-drop limits

Branch circuits (outlets, lighting): 3% max. Feeder circuits (subpanels): 5% max. Combined branch + feeder: 5% total. Sensitive electronics: 1% or less. These are NEC-recommended targets, not hard limits, but exceeding them risks dimming lights, sluggish motors, or misbehaving electronics.

Copper vs. aluminum wire

Aluminum conductors have roughly 61% the conductivity of copper (higher resistance for the same size), so an aluminum run typically needs to be 1-2 gauge sizes larger than copper to carry the same current with the same voltage drop. Aluminum is lighter and cheaper for long, high-current runs, which is why it is common in service entrances and feeders.

Why three-phase changes the math

Single-phase voltage drop uses a factor of 2 (current flows out and back on two conductors). Three-phase balanced loads use √3 (≈1.732) instead, because the phase currents partially cancel — so a three-phase circuit typically shows a lower voltage drop than a single-phase circuit carrying the same current over the same distance.

Features

One unified screen: Quick calculation based on current, distance, and voltage — no mode to pick first.

NEC Compliance: Expandable section for temperature rating and installation method, checked against standard ampacity tables.

Advanced Environment: Expandable section for phase type and ambient temperature, with full derating and power-loss detail.

Material Options: Compare copper vs aluminum and select installation method (conduit, buried, free air).

Ampacity Lookup: Pick a wire gauge and see the maximum amps it is rated to carry, using the same conductor, insulation rating, installation method and ambient temperature — the reverse of sizing.

Common Use Cases

Home Electrical Projects: size wiring for new circuits or additions, ensure safe installation that meets code, and prevent voltage drop and equipment damage.

Professional Installation: calculate wire gauge for commercial systems, comply with NEC and local codes, and compare copper vs aluminum conductors.

Industrial & Heavy Duty: design high-current power distribution, account for temperature and installation method, and optimize for cost while ensuring safety.

Troubleshooting & Upgrade: diagnose voltage drop problems, upgrade undersized circuits, and plan capacity for future loads.

Ampacity Check: answer "how many amps can 12 gauge wire handle" for the wire you already have, with the NEC ambient derating applied rather than the raw table figure.

Frequently Asked Questions

Enter current, run distance, and voltage. Heavier loads and longer distances need thicker wire (lower AWG number). Expand NEC Compliance to set temperature rating and installation method, or Advanced Environment for phase type and ambient temperature — both are optional sections on the same screen, not separate modes.
A common NEC guideline is 3% for branch circuits and 5% combined for feeder + branch. Safety Review mode includes quick 3%/5% targets so you can test both scenarios quickly.
A 20-amp circuit requires a minimum of 12 AWG copper wire (NEC 310.15). For long runs where voltage drop is a concern, you may need to upsize to 10 AWG. Enter your specific amperage and run length in this calculator to confirm the correct size.
Yes. Aluminum wire has about 61% the conductivity of copper, so it requires a larger AWG for the same current capacity. Aluminum is commonly used for service entrance and large feeder circuits. Select your conductor material in Advanced mode for accurate sizing.
A 50-amp circuit typically needs 6 AWG copper or 4 AWG aluminum for a standard run, based on the NEC 60°C/75°C ampacity tables. Long runs can require upsizing to keep voltage drop under 3%. Enter 50 amps with your actual run length and conductor material above to confirm the correct gauge for your installation.

Related Calculators

Last updated